Videos/Podcasts

Are We Designing Laboratories for Science or for Assumptions?

Presenter: Michelle Rittmann, LEED AP, Senior Mechanical Engineer, Genesis AEC
Event: Lab Design Digital Conference: HVAC Design for a Sustainable Lab (November 12, 2026)
Continuing Education: AIA CES Approved (1 LU/HSW

How Scientific Workflows Drive Sustainable Lab Design

A laboratory suite holds 135 pieces of research equipment and never has more than four people working inside at once. Calculated from electrical nameplate data, the space required 51 kW of cooling and 10,000 CFM of airflow. After the engineering team sat down with the scientists to review how that equipment actually runs, the heat load dropped to 19.7 kW, and airflow fell to 4,505 CFM

For Michelle Rittmann, LEED AP, Senior Mechanical Engineer at Genesis AEC, that 55% airflow reduction shows what happens when design teams stop sizing systems around worst-case guesses and start designing around real scientific work.

Start with the Science, Not the Room Label

Most discussions around sustainable laboratory HVAC focus on energy recovery and equipment efficiency once a system is already sized. Michelle points to an earlier, higher-impact moment: how project teams define requirements during programming. A floor plan label like “lab” or “lab support” tells an engineer almost nothing about what happens at the bench. Processes drive HVAC loads, not room names.

Individual assumptions about occupancy, ventilation rates, future growth, reliability, flexibility, and hazard levels often sound reasonable on their own. Stacked together, they compound into mechanical infrastructure built for operating conditions that never happen, locking in excess capacity, energy waste, and maintenance burdens for the next 30 years.

How Three Load Calculations Produced Three Very Different Systems

In the suite Michelle examined, both rooms required Grade D cleanroom classifications, meaning air change rates were fixed and validated. Because validated spaces leave little room for wide airflow turndown, oversizing cannot simply be handed off to building controls to fix later. Yet three standard ways of estimating the exact same 135-piece equipment list yielded dramatically different mechanical designs:

Equipment Heat Load Comparison (135 Pieces of Equipment)

  • Electrical Nameplate Data (51 kW): Raw electrical ratings produced a 10,000 CFM airflow requirement.
  • Manufacturer Catalog Data (25 kW): Published thermal output cut the estimate roughly in half.
  • Scientist Workflow Review (19.7 kW): Spending 60 to 90 minutes with the scientists to separate 24/7 equipment from intermittent benchtop tools brought airflow down to 4,505 CFM.

Flexibility Is Not Free

Every lab owner wants a facility that can evolve, but Michelle urges project teams to draw a sharp line between flexibility and adaptability. Designing every suite for every conceivable future scenario forces larger mechanical shafts, higher first costs, extra utility distribution, and oversized air handlers, all of which carry immediate financial and embodied-carbon penalties. Adaptability means planning realistic pathways for future change without building unused infrastructure on day one.

The objective is never a less safe, less reliable, or less capable laboratory. It is hitting those exact performance targets intentionally rather than by default.

Sustainable HVAC Starts Before Mechanical Sizing

Architectural layout, space planning, and equipment selection shape thermal loads long before a mechanical engineer runs a calculation. In almost every research environment, scientific instruments, not people, drive the cooling load. Understanding how scientists actually use those instruments is the single most reliable way to right-size a facility.

Watch the Full Presentation

Originally presented at Lab Design’s HVAC Design for a Sustainable Lab Digital Conference (November 12, 2026), this AIA CES-approved session walks through the 135-item equipment audit, Grade D airflow constraints, and practical steps project teams can apply during early programming.

About the Speaker

Michelle Rittmann is a Senior Mechanical Engineer at Genesis AEC, with over two decades of experience designing high-performance, sustainable HVAC systems for complex laboratory and life sciences facilities. She specializes in right-sizing mechanical systems to balance strict safety and contamination control standards with long-term energy efficiency and operational flexibility. She is a LEED Accredited Professional and holds a Bachelor of Science in Mechanical Engineering from The Johns Hopkins University.

 

 

About Genesis AEC

Genesis AEC – an award-winning consulting, architecture, engineering, and construction management firm – has partnered with life sciences companies for more than 25 years to complement the scientific expertise of our clients as they usher in the next generation of life-saving therapies, treatments, and technologies. Whether it’s providing AE support for existing sites; commissioning, validation, and qualification (CQV) for specific processes or equipment; or turnkey design-build solutions, our team blends sound science and technical expertise with quality assurance and safety measures to deliver unparalleled results.